Call us today: 416.292.0599

Services

SPRINKLER PROJECTS:

The Ontario Fire Code and the National Fire Code both mandate annual inspections and testing of Fire Sprinklers to National Fire Protection Association (NFPA) Standard 25.

Qualified & trained personnel must carry out fire sprinkler system safety inspections and testing.Our customers know with confidence that…

Harding Fire Protection will perform fire sprinkler inspections to the highest industry standards, complete with certification and cutting edge documentation.

Standard wet pipe sprinkler systems to state of the art complex multi- facetted systems.

  • Wet pipe sprinkler systems (office and plaza complexes)
  • Dry pipe system (parking garages)
  • Pre-action sprinkler systems (computer rooms)
  • Two stage or double interlock sprinkler systems (Telecom Facilities)
  • Specialty systems: Mist, Vesda, FM200, and Argonite etc.
  • Sprinkler and standpipe fire pumps performance testing.
  • Fire hose inspection and testing

Exposed sprinkler piping hangers should be inspected annually to ensure that they are kept in good repair.6.5.3.2.

Sprinkler heads shall be checked at least once per year to ensure that they are free from damage, corrosion, grease, dust, paint or whitewash.6.5.3.5.

Water supply pressure and system air, or water pressure should be inspected by using gauges to ensure that the system is maintained and are at the required operating pressure.6.5.3.3.

Dry-pipe valve rooms or enclosures in unheated buildings should be inspected as often as necessary when the outside temperature falls below 0oC to ensure that the system does not freeze.6.5.3.4. Auxiliary drains shall be inspected to prevent freezing. 6.5.4.1.

Auxiliary drains shall be inspected to prevent freezing. 6.5.4.1.Water flow alarm tests using the most hydraulically remote test connection shall be performed annually on wet sprinkler systems.6.5.5.3.

Dry-pipe valves should be trip tested annually.6.5.5.4.(2)

Sprinkler system water supply pressure should be tested annually with the main drain valve fully open to ensure that there are no obstructions or deterioration of the main water supply.6.5.5.5.

Fire Pump Inspection

Fire pumps should be tested annually at full rated capacity to ensure that they are capable of delivering the rated flow.6.6.3.5.

Fire Hose & Standpipe Inspection

Plugs or caps shall be removed annually and the fire department connections inspected for wear, rust or obstruction and corrective action shall be taken as needed.6.4.1.3.(2)

Hose stations should be inspected monthly to ensure that the hose is in proper position and that all of the equipment is in place and in operable condition.6.4.2.1.

Hose valves should be inspected annually to ensure that they are tight so that there is no water leakage into the hose.6.4.2.4.

Standpipe hose should be inspected and re-racked annually and after use, and any worn hose or gaskets in the couplings at the hose valves and at the nozzle replaced.

When hose is re-racked as required in Sentence (1), it shall be done so that any folds will not occur at the same places.6.4.2.5.(1)

Backflow Prevention

The flow back of water or reversal of the normal flow. If backflow occurs in a public water system, the action can pollute or contaminate the water in that system creating a health hazard for consumers. The Ontario Building Code (OBC) does require backflow protection to be in place wherever a potential cross-connection has been identified on a property. This is to be done every 5 years.

We’ve Got You Covered
  • Harding Fire Protection is a compliance-focused organization. From our Health and Safety program, to our ISO 9001:2008 certification, we guarantee you are working with a professional organization, who meets all your compliance requirements.
  • We hold accreditations from Contractor Check, ComplyWorks, Cognibox and other contractor-compliance vendors.
  • In addition, all of our staff are CPIC cleared and we have Reliability Status with the Government of Canada (PWGSC).

Request a free

consultation today!

Simply fill out the form below and a representative will be in contact with you as soon as possible.
Have a great day!